Key Features:
1. High-efficient DSP chip
2. Outstanding electric property
3. Good looking and excellent hardware
4. N+X parallel redundancy (compatible to battery share in the parallel mode)
5. Frontal-board operation and maintenance
6. Twin-channel line input
7. Remote monitoring
8. Intelligent management of battery charging and discharging
9. Flexible battery arrangement
10. Flexible arrangement, change due to the need.
Model # |
GP33 series |
||||||||||
Capacity |
10KVA |
15KVA |
20KVA |
30KVA |
40 KVA |
60KVA |
80KVA |
100KVA |
120KVA |
160KVA |
200KVA |
INPUT |
|||||||||||
voltage |
(208/308/400/480Vac) ± 20% / 5 wires (3 lines + neutral + ground) |
||||||||||
frequency |
50/60Hz ± 10% Auto sensing |
||||||||||
power factor |
0.98 |
||||||||||
filter |
EMI, RFI |
||||||||||
dual input |
optional |
||||||||||
OUTPUT |
|||||||||||
voltage |
(208/308/400/480Vac) ± 20% / 5 wires (3 lines + neutral + ground) |
||||||||||
frequency |
50/60Hz ± 1% Auto sensing |
||||||||||
Efficiency |
AC/AC>92% |
||||||||||
transfer time |
0 ms |
||||||||||
wave form |
sine wave |
||||||||||
power factor |
0.8 |
||||||||||
voltage T.H.D. |
<2% with linear load |
||||||||||
crest factor |
3:1 |
||||||||||
technology |
true on-line double conversion controlled by microcontroller |
||||||||||
overload recovery |
automatically transfer to UPS mode |
||||||||||
Isolation transformer |
inverter mode (bypass mode is optional) |
||||||||||
parallel connection |
parallel connection function is ready (extra PCB is not reuired) |
||||||||||
BATTERY |
|||||||||||
battery type |
VRLA (valve regulated lead acid), not included |
||||||||||
DC voltage |
384 Vdc |
||||||||||
charging time |
4 hours up to 90% |
||||||||||
battery detection |
self-detect, transfer to battery mode adjustable |
||||||||||
PROTECTION |
|||||||||||
lightning and transient protection |
hot swappable lightning and transient surge suppressor (in:10Kamp, Up:1.5 Kv, I max: 20 Kamp.) |
||||||||||
harware protection |
input breaker, output breaker, battery breaker, bypass breaker; DC fuse, fan, redundant power supply; temperature sensor, EPO (Emergency Power Off), audible alarms etc. |
||||||||||
software protection |
discharging batteries, battery charger working mode, inverter working mode, emergency power off, manual shutdown, bypass SCR failure, bypass sequence failure, bypass over the limit, critical overload, batteries exhaustion, low or high output voltage, DC fuse open, 5V power supply failure, 13.5 power supply failure, inverter overvoltage, 200% overload on each line, transfer failure, inverter voltage out of range, over voltage betweenneutral and ground, UPS on bypass mode, bypass frequency out of range. |
||||||||||
bypass |
solid state |
||||||||||
overload |
125% for 10min, 150% for 30sec, 1000% for 16 millisecond |
||||||||||
EPO |
EPO local and/or remote |
||||||||||
Display |
LCD, touch screen |
||||||||||
LED diagram |
included |
||||||||||
communication |
RS232 intelligent slot, modem, SNMP(RJ45) (SNMP adaptive software is supplied by the producer) |
||||||||||
ENVIRONMENT |
|||||||||||
elevation |
1.700 m.o.s.l without derrating |
||||||||||
temperature & noise |
0℃~40℃/<60dB @1.5m. |
||||||||||
humidity |
0~95% non condensate |
||||||||||
PHYSICAL |
|||||||||||
Unit dimension (mm) |
L830*W402*H1050 |
L664*W865*H1548 |
L966*W890*H1748 |
L1160*W1043*H1900 |
|||||||
Net weight (1pc, kg) |